IEEE
SYSTEM GROUNDING Std 142-2007
If a delta tertiary is added to a wye-wye transformer it will not be necessary to supply
zero-sequence current from the primary source, since the tertiary will act as a source of
zero-sequence current.
Thus, the wye-wye transformer can be considered a part of a single multi-voltage system
if the neutrals are interconnected or can be considered to create a separate system if they
are not. The symmetry of the wye-wye allows it to provide grounding for its load-side
system even though the source and load side may be interchanged at any time.
1.6.5 Single power source
When a system has only one source of power (generator or transformer), grounding may
be accomplished by connecting the source neutral to earth either directly or through a
neutral impedance (Figure 1-22). Provision of a switch or circuit breaker to open the
neutral circuit is not recommended. It is not desirable to operate the system ungrounded
by having the ground connection open while the generator or transformer is in service.
In the event that some means of disconnecting the ground connection is required for
measurement, testing, or repair, a disconnecting link should be used and only opened
when the system is de-energized.
Figure 1-22—Grounding for systems with one source of power: (a) solidly
grounded, (b) R or Z grounded.
1.6.6 Multiple power sources
For installation of interconnected multiple power sources (i.e., generators or power
transformers), operated in parallel, system grounding can be accomplished using one of
the two following methods:
a) Each source grounded, with or without impedance (Figure 1-23)